Quantcast
Channel: Modicon / Telemecanique / Schneider Electric Latest Topics
Viewing all 446 articles
Browse latest View live

EcoStruxure - Lexium32 power enable issue

$
0
0

Hi,

 

i have a plc  M262 Schneider and try with Schneider Ecostruxure to power enable a lexium32...  Normally with SOMACHINE 4.3 i have no problem. Anybody have a ways??

 

 

Thanks


M580 sd card install

$
0
0

Just received my blank Schneider sd card it's already formatted. Program is already on the M580 so if I insert, will it write the program to it automatically and save? or do I need to put the plc in stop mode, insert, then put back into run mode? or must I do a project backup and backup save.

Modicon TSX Micro 3721001 - CPU Fault - Modules or Base Unit?

$
0
0
Hello - we run a car wash that is controlled by a Modicon TSX Micro 3721001. It is indicating a CPU fault. I've attached a picture of the unit in place, with the LEDs lit. I have ordered a new base unit (2nd picture). I haven't tried it out yet, but it is tested working. I am hoping a base unit replacement will solve the problem, but wondering if it it possible the problem could be in the modules? I did not order those but now wondering if I should have... If the issue could be with the modules, is there a way to test which one it would be so I won't need to order all 4? If it coult be a module, I might order that now as I am in a rush to get back in service. Thanks for any guidance! Andy

Communication

$
0
0

Hello.

I am having 22 slaves communicating to a master on rs485 half duplex.i have selected baud rate as 38400 on a length of 800m.The problem is out of 22 devices only six are communicating .i have checked wiring,inserted termination resistor but still not getting rest of the devices alive.is it that i have selected high baud rate on a long length?this is the only problem as i am seeing it.can somebody help me on this issue

Modicon M241 Firmware

$
0
0

Dear All,

TM241CE40R is installed with firmware 4.0.3.18

If I buy new CPU with some other firmware, will it work or I will need to change the firmware?

 

Counting on time

$
0
0

Hello!

Anyone have tips for getting a precise count in seconds for the «on time» of a input?

water pump deliveres 20 l/min and input is feedback that its running.

ive been trying with %s4-6 and input in serial but not getting it precise

Somachine basic

PID or Not PID ! , Relaxc ?

$
0
0

Hi,
I propose a free trial version of new methodology of process control ( Relaxc)  under expert control of schneider.
If you are a school, technician, student, or an industrial, you can test it and compare it to your controllers.
Inside the package you have the practical guide of relaxc that allows to control quickly all your processes.
If you have the time to test it, i would like a feedback or share your feedback on the post. It is important for me
https://www.appedge.com/pdffile/relaxc_expertcontrol.pdf

To download you have 3 ways, but it is necessary that you give few information to get it.

https://shop.exchange.se.com/en-US/apps/55444/relaxc---critical-process-loop-control---trial-version
https://www.researchgate.net/publication/339781285_Appedge_relaxc_demo_v1
or
relaxc@appedge.com

enjoy it

relaxc

MachineExpert Vijeo Designer simulation

$
0
0

Hi guys,

I installed new MachineExpert v1.2 and Vijeo 6.2.9 on Win10 machine. When connecting simulation PLC to Vijeo to test my application everything is good.
I go to PLC and check the nodename (see the pic attached) which I put in my Vijeo application and everything works. Issue is, because of my hard drive capacity I am forced to work via VM (but this is my preffered way also because of number of PLC softwares used). When I installed from the same installer (everything same as my local Win10) on Win7 VM when I run simulation I get empty space where the PC simulator should be visible which nodename I should type in Vijeo.
Also I noticed when going to gateway management console in VM the process is active, same parameters as in host machine. Turning off the gateway on the VM turns it off as well on the host.
Is there a known problem of connecting to simulator on VM? Or win10? Unfortunately I don't have Win10 VM to try right now..
Anyone can help? Much appreciated!

Machine Expert Logic Builder.png


Problem with program HMIGTO5310 Versus XBTGT5320

$
0
0

Need your helps Guys,

My XBTGT5320 was defective, then i want to replace with HMIGTO5310. My questions:

1. Can i use the old program (firmware V6.1), downloaded to new HMIGTO5310 (firmware V0.3)? How?

2. What version of Vijeo Designer that i should use?

Thank you for all your helps.

Zelio Ethernet

$
0
0

Hi All,

 I’m trying to get 2 SR3B262BD’s to communicate with each other, using 2 Ethernet expansion modules, so that the inputs from one control the outputs of the other. 
 Is this actually possible ?. As far as I can tell, I’ve created a program that, I think, should work. Any help would be very gratefully received. 
  Thanks,

   Northman. 

Issue transferring project from Pro face HMI.

$
0
0

Hello, I am having an issue transferring a project from a Proface HMI Model: PS-3711A to my laptop.

I am connected through ethernet and using the same subnet, when I load the Transfer tool from Win Pro EX (version 4.09) and select the receive button it launches a window that seaches for my HMI which it is able to successfully locate.  When I select the HMI from the auto search window, it connects and begins to transfer data, where it gets stuck at "Receiving Project" forever.  Tried just about everything I can think of.

I normally work with rockwell so I am not very familiar with pro-face products.  Just wondering if anyone else has encountered the same issue, or had any ideas for getting around it.

 

Thank you

Problem "Electric soft starter"

$
0
0

I have a digital soft starter altistart 48 telemecanique shneider, the problem is it works 10 seconds and turns off! I idont know why?!

Connection Between Two RIO panels

$
0
0

Dear Experts,

I have two M580 remotes I/Os panel and CPU panel and I want to connect all by using BMXNRP0200 Fiber Converter modules. In IO panels the backplane is BME XBP 1200, after the CPS3500 at slot "0" I have installed CRA 312 module and then all other IO modules AMI, AMO, DDI & DDO. My question is: at which slot on the backplane I need to insert BMXNRP0200 in IO panels and at which slot in the CPU panel and how I need to make ethernet and fiber connection on the module. It has two ethernet ports up and down and two fibre ports up and down. Which ethernet port (up or down) I need to use to connect with CRA and which fiber port (up or down) I can use to connect with another BMXNRP0200 Fiber Converter installed in another panel. I have attached the snap of configuration where I have CPU panel and two remote IO panels ? 

Best Regards,

Ahmed

 

Mian CPU Panel.png

 

 

IO Panels.png

BMXNRP0200.png

Lee

$
0
0

Hi ya, 

can someone please advise if it is possible to add a text box that the user can enter a name / description to. 
I am hoping the user can select the text box and a pop up keyboard will appear for them to enter a description on a magelis hmi. 
I look forward to your advise. 

Serial Output

$
0
0

Hello.  I am new to programming with a Modicon 340.  I would like a serial output to a printer (or an LCD screen) (eg) an input is registered and I would like an output to display the results of the input.  Does the Modicon 340 support this?  I have the P3420302 module which appears to have a serial connection (along with ethernet).  If someone could point me in the right direction I would greatly appreciate it.


citect message function

$
0
0

Please help me to change the font size in 'message ()' function of citect cicode

Excel Export of Alarms in Citect SCADA 7.50.

$
0
0

Hello,

I am new to Scada Programming. I am using Citect scada V7.50. I have completed whole project, but I am unable to generate Excel report for Alarms generated during run time.

Please help me for this issue.

Thanks...

schneider M580

$
0
0

Hello,
I would like to replace my DRA1605 output module (faulty, ERR light on) on my M580, can I turn my PLC off without losing the program and data.
thanks in advance

Unity pro Upload simple question

$
0
0

Qucik question guys, im a noob on Unity Pro and was wondering if uploading a project off of a plc already running a program will affect the operation of the already program?

Proworx32 and Remote Rack Power supplies

$
0
0

Hi,

Have on older Quantum PLC that I am new to and had to change out power supplies.  We had redundant 140CPS12400 power supplies and one was failing in service and was alarming constantly to our DCS HMI.  Our local storehouse had the replacement 140CPS12420 supplies but found out from Schneider that both supplies on the remote rack needed to be changed as the new models do not play nice with the older ones.

I replaced the modules successfully and the rack has full power restored with all modules happy.  The problem remaining is that the status of the new supplies in Proworx32 has flagged both supplies as failed and hence sends alarms to our DCS system that both have failed.  Is there a reset of some sort in the PLC program?  I looked through the program to see if there was a hardware configuration change required to let the system know of the new part number but came up empty.  I traced the ladder logic back to the STAT command from the processor.

I am hoping that there is a reset somewhere that I am missing.  Everything if functioning normally but I would not get a failure alarm if one was to fail.  Any help would be greatly appreciated.

Thanks,

Lee. 

Viewing all 446 articles