M340 NOE IO Scanning of DSE 8610 Gen Contyroller

$
0
0

I am having issues with M340 IO scanning. I have the NOE card next to the CPU which is a 2020 item. I have set the Network for the CPU as 192.168.0.5 and the NOE card as 192.168.0.12. To the NOE card I have connected a Deep Sea Electronics 8610 MkII generator controller which has configurable modbus pages. Its IP is 192.168.0.3. I have set the IO scan tab of the NOE to read the device at 192.168.0.3 starting at remote address 442497 (Page 166 of the DSE, 166*256). for 80 registers and to store them in PLC at %MW300 onward. When compiled this read works perfectly with values being loaded. The problem comes when I try a second read from the same device. This time Page 167 (167*256) at address 442753 which is sent to local PLC %MW380 onward. Now when I compile the code the first page is read OK as prior but the second read shows a "Faulty/Absent" on teh IO scanner debug page and no values are read. If I change the first entry to scan page 167 with page 166 deleted, again all is OK. It seams I am unable to make more than one read of the DSE product. I have spoke with DSE whom state the device can have multi reads from multiple masters and they have proved multiple reads from the same and different devices. I am now at a loss as to what to try next. I hope somebody can provide some insight. I also tryed doing teh second read with a standard READ_VAR command with teh same result. Just wondering if its a NOE thing or a set up thing I have missed.

20180911_144113.jpg